Range name | EasyPact CVS |
Main function | Moulded Case Circuit Breaker (MCCB) |
Sub-range name | CVS100B |
Rated Voltage (AC) - Phase-to-phase | 440 V |
Rated impulse voltage (Uimp) | 8 kV |
Rated insulation voltage (Ui) | 690 V |
Rated current | 63 A |
Frame current rating | 100 AF |
Trip current rating | 63 AT |
Ultimate short circuit current breaking capacity (Icu) | (220-240Vac) 40 kA |
| (380-415Vac) 25 kA |
| (440Vac) 20 kA |
Service short circuit current breaking capacity (Ics) | (220-240Vac) 40 kA |
| (380-415Vac) 25 kA |
| (440Vac) 15 kA |
Service short circuit current breaking capacity as a percentage of Icu | (Ics%)(380-415Vac) 100 % |
Poles | 3 Pole(s) |
Protected poles | 3 Pole(s) |
Utilisation category | A |
Compliant with standard(s) | IEC60947-2 |
| IEC60664-1 |
Electrical durability (with load) | (415Vac; In/2) 30000 operations |
| (415Vac; In) 12000 operations |
Mechanical durability (at no load) | 30000 operations |
Degree of pollution | 3 |
Trip unit type | TMD |
| Thermal-Magnetic (adjustable) |
Protection function | Thermal protection (Overload) |
| Magnetic protection (Short-circuit) |
Protection settings | (Over-current) adjustable from 0.7 - 1.0 x In |
| (Short-circuit) fixed at 500A |
Type of terminals | Lug |
Functions | Moulded Case Circuit Breaker (MCCB) |
Primary brand | Schneider Electric |
Secondary brand | Merlin Gerin |