LOADING IMAGES
KETERANGAN PRODUK
Brand |
: |
SCHNEIDER |
SKU |
: |
SCH-03126-AMP-PCS-BLC |
Ref Number |
: |
LV540319 |
Satuan |
: |
PIECES |
Berat |
: |
1000 Gram |
Dilihat |
: |
351 Kali |
Deskripsi
Moulded Case Circuit Breaker (MCCB) - Schneider Electric (EasyPact CVS) - CVS400N TMD 400A 4P3d - 4 poles (4P3d) - Rated current 400A - Short circuit breaking capacity (Icu) (380-415Vac) 50kA - Thermal-Magnetic (adjustable) trip unit (TMD) - Lug terminals
Spesifikasi
Range name | EasyPact CVS |
Main function | Moulded Case Circuit Breaker (MCCB) |
Sub-range name | CVS400N |
Rated Voltage (AC) - Phase-to-phase | 440 V |
Rated impulse voltage (Uimp) | 8 kV |
Rated insulation voltage (Ui) | 690 V |
Rated current | 400 A |
Frame current rating | 400 AF |
Trip current rating | 400 AT |
Ultimate short circuit current breaking capacity (Icu) | (220-240Vac) 70 kA |
| (380-415Vac) 50 kA |
| (440Vac) 42 kA |
Service short circuit current breaking capacity (Ics) | (220-240Vac) 70 kA |
| (380-415Vac) 50 kA |
| (440Vac) 32 kA |
Service short circuit current breaking capacity as a percentage of Icu | (Ics%)(380-415Vac) 100 % |
Poles | 4 Pole(s) |
Protected poles | 3 Pole(s) |
Utilisation category | A |
Compliant with standard(s) | IEC60947-2 |
| IEC60664-1 |
Electrical durability (with load) | (415Vac; In/2) 12000 operations |
| (415Vac; In) 6000 operations |
Mechanical durability (at no load) | 15000 operations |
Degree of pollution | 3 |
Trip unit type | TMD |
| Thermal-Magnetic (adjustable) |
Protection function | Thermal protection (Overload) |
| Magnetic protection (Short-circuit) |
Protection settings | (Over-current) adjustable from 0.7 - 1.0 x In |
| (Short-circuit) adjustable from 5 to 10 x In |
Type of terminals | Lug |
Functions | Moulded Case Circuit Breaker (MCCB) |
Primary brand | Schneider Electric |
Secondary brand | Merlin Gerin |
PRODUK KATEGORI BERDASARKAN BRAND